153
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.4.7 Distance (D910)
This indicates the distance from the transmitter face to a detected surface.
It is a useful diagnostic because a false surface signal can be identified and related to the physical
nature of the installation.
Note
Figure F-1 on page 106 shows this parameter in a tank geometry illustration.
Field Communicator
To view the distance to a detected surface:
1. From the Home screen, select 3: Service Tools.
2. Select 1: Alerts.
3. Select 2: Diagnostic Data.
4. Select 1: Target Data.
5. Select 1: Distance D910.
6. When finished, press EXIT to exit to the previous menu.
Mobrey MCU900 Series control unit
To view the distance to a detected surface:
1. From the Main Menu screen, select MONITOR.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select DIAGNOSTICS.
4. Select Distance.
5. When finished, press the ESC key to exit to the previous menu.
Fast Keys
3, 1, 2, 1, 1
Distance D910
2.327 ft
EXIT
HELP
(Field Communicator Screen)
Distance D910
2.227ft
(Mobrey MCU901 Screen)