Section 4: Starting up
February 2015
Note
If the existing data entered allows the transmitter to calculate the maximum flow,
the 4 mA and 20 mA points are set to 4 mA at zero flow and 20 mA at maximum flow.
4.2.8 Maximum level entry
Screen display: LEUEL @ max
Factory default value: 1.000
This menu option is offered if the selected duty is Flow and requires the level to be entered at
which the maximum flow occurs.
Note
This menu option is in the programming menu. See Figure C-1 on page 76 for a map of
the menu structure and how to access the menu options.
To change the Level@max value
1. If entering the menu system from the PV display, press the green button repeatedly
until the “LEUEL @ max” menu is indicated (see above note).
2. Press the blue button
to enter the “LEUEL @ max” menu and display the present
Level@max value.
3. If the indicated value is correct, press the red button
to exit to the menu.
(The “LEUEL @ max” re-appears. To get to the next menu, press
4. Press the blue button to start the editing mode. The first digit flashes to indicate it
can now be edited.
5. Press the green button
repeatedly to edit the flashing digit.
6. Press the blue button
to move to the next digit. The digit flashes to indicate it can be
edited.
7. Repeat steps (5) and (6) until the last digit is flashing, and edited as required.
8. Press the blue button
to confirm the new value. (The flashing stops.)
9. If the new value is correct, press the red button
to save. The display changes to the
next menu option.
10. If the new value is incorrect, press the blue button
to exit to the menu.
11. The menu option “LEUEL @ max” re-appears to re-start at step (2) or press
for the
next menu option.