Emerson Mobrey MSP400RH and MSP900GH Marine Radio User Manual


 
139
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.3.34 Target pulses (P044)
Target Pulses (P044) is the number of ultrasonic pulses in each burst sent from the transmitter
every second.
The factory default “Automatic” setting allows the transmitter to decide the number of
pulses. Alternatively, select a number in the range 4 to 32.
Note
See Pulses in Use (page 161) for the actual number of pulses used.
Field Communicator
To view or change the number of pulses in a burst:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 7: Advanced Processing (MSP900GH) or
Select 8: Advanced Processing (MSP400RH)
4. Select 5: Set Target Pulses.
5. Select 1: Target Pulses P044.
6. If a change is required:
(a) Select a new setting, and then select “ENTER” to save it.
(b) Press “SEND” to update the transmitter.
Mobrey MCU900 Series control unit
To view or change the number of pulses in a burst:
1. From the Main Menu screen, select SETUP.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select ENGINEERING, and then ADVANCED.
4. Select Target Pulses.
5. Follow the on-screen instructions to edit and save the new setting.
(Press the Enter ( ) key if prompted to change mode to “off-line”).
6. Select “Quit” to exit to the previous menu.
Fast Keys
2, 2, 7 [or 8], 5, 1
Target Pulses P044
AUTOMATIC
27
28
29
30
31
32
AUTOMATIC
AUTOMATIC
ENTER
ESC
(Field Communicator Screen)
Target Pulses P043
Automatic
Esc=Quit =Edit
(Mobrey MCU901 Screen)