143
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.3.38 Clear false echoes (P089)
This is used to clear a specified False Echo Data record, or clear all of the False Echo Data records.
Field Communicator
To clear false echo data:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 6: False Echoes (MSP900GH)
or 7: False Echoes (MSP400RH).
4. Select 5: Clear False Echoes.
5. Select “All” or a numbered false echo record,
and then press “ENTER” to confirm the selection.
6. Press “SEND” to update the transmitter.
Note
When messages appear, take appropriate action if needed and press “OK”.
Mobrey MCU900 Series control unit
To clear false echo data:
1. From the Main Menu screen, select SETUP.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select ENGINEERING,
and then select FALSE ECHO ACTION.
4. Select Clear False Echoes.
5. Select “Edit” ( ), then select an option using the up-arrow or down-arrow keys, and
finally select “Save” ( ) to confirm the selection.
(Press the Enter ( ) key if prompted to change mode to “off-line”).
6. When finished, select “Quit” to exit to the previous menu.
Fast Keys
2, 2, 6 [or 7], 5
Select false echo to clear
False Echo 1
False Echo 2
False Echo 3
False Echo 4
All
All
ENTER
ESC
(Field Communicator Screen)
Clr False Echo P089
Esc=Quit =Edit
(Mobrey MCU901 Screen)