February 2015
To set the 4 mA level
1. If entering the menu system from the PV display, press the green button repeatedly
until the “SEt 4” menu option is indicated (see note on the previous page).
2. Press the blue button
to display the PV at 4 mA.
3. If the value is correct, press the red button
to exit to the menu.
(The “SEt 4” re-appears. To get to the “SEt 20” menu, press
).
4. With the transmitter aimed at a target a distance away equivalent to the 4 mA level,
press the blue button
to start the ranging. The display alternately flashes “4” and the
live measurement reading.
5. Press the blue button
to confirm the PV at 4 mA is to be changed to the same value as
the live measurement reading.
6. If the new PV at 4 mA value is correct, press the red button
to save and then the green
button
to get to the “SEt 20” menu.
7. If the new PV at 4 mA value is incorrect, press the blue button
to exit to the menu.
8. The menu “SEt 4” re-appears to re-start at step (2) or press
to get to the
SEt 20” menu.
Note
This “SEt 20” menu option is in the programming menu. See Figure C-1 on page 76
for a map of the menu structure and how to access the menu options.
To set the 20 mA level
1. If entering the menu system from the PV display, press the green button repeatedly
until the “SEt 20“menu option is indicated (see note above).
2. Press the blue button
to display the PV at 20 mA.
3. If the value is correct, press the red button
to exit to the menu.
(The “SEt 4” re-appears. To get to the next menu, press
.)
4. With the transmitter aimed at a target a distance away equivalent to the 20 mA level,
press the blue button
to start the ranging. The display alternately flashes “20” and
the live measurement reading.
5. Press the blue button
to confirm the PV at 20 mA is to be changed to the same value
as the live measurement reading.
6. If the new PV at 20 mA value is correct, press the red button
to save and then the
green button
to exit the menu system and return to the PV display.
7. If the new PV at 20 mA value is incorrect, press the blue button
to exit to the menu.
8. The menu “SEt 20” re-appears to re-start at step (2) or press
to exit the menu
system and change to the PV display.