Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 4 Explanation of Functions
4 - 78
(4) Basic display mode
The monitor displays basic parameters. (The monitor display is the factory setting.)
The following table lists the parameters that can be displayed in basic display mode:
No. Code displayed Item
1 d001 to d104 Monitoring indication
2 F001 Output frequency setting
3 F002 Acceleration (1) time setting
4 F003 Deceleration (1) time setting
5 F004 Keypad Run key routing
6 A001 Frequency source setting
7 A002 Run command source setting
8 A003 Base frequency setting
9 A004 Maximum frequency setting
10 A005 [AT] selection
11 A020 Multispeed frequency setting
12 A021 Multispeed 1 setting
13 A022 Multispeed 2 setting
14 A023 Multispeed 3 setting
15 A044 V/F characteristic curve selection, 1st motor
16 A045 V/f gain setting
17 A085 Operation mode selection
18 b001 Selection of restart mode
19 b002 Allowable under-voltage power failure time
20 b008 Selection of retry after trip
21 b011 Retry wait time after trip
22 b037 Function code display restriction
23 b083 Carrier frequency setting
24 b084 Initialization mode (parameters or trip history)
25 b130 Overvoltage suppression enable
26 b131 Overvoltage suppression level
27 C021 Terminal [11] function
28 C022 Terminal [12] function
29 C036 Alarm relay active state
4.2.85 Initial-screen selection (selection of the initial screen to be displayed after
power-on)
The initial-screen selection function allows you to specify the screen that
is displayed on the digital operator immediately after the inverter power is
turned on. The table below lists the screens (items) selectable. (The
factory setting is "01" [d001].)
To adjust the screen selection setting of your SJ700 series inverter to an SJ300 series inverter, select "00"
(the screen displayed when the STOP/RESET key was last pressed).
Item Function code Data Description
00 Screen displayed when the STR key was pressed
last (equivalent to the setting on SJ300)
01 d001 (output frequency monitoring)
02 d002 (output current monitoring)
03 d003 (rotation direction minitoring)
04 d007 (Scaled output frequency monitoring)
Initial-screen selection b038
05 F001 (output frequency setting)
Note: When "00" (the screen displayed when the STR key was last pressed) has been selected, the
monitor displays code "*---" (entry to a group of functions) if the functional item displayed last is not
"d***" or "F***".
(Example) If the inverter power is turned off immediately after the setting of "A020" has been
changed, the monitor will display "A---" as the initial screen after the next power-on.
b038: Initial-screen selection
Related code