Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 4 Explanation of Functions
4 - 147
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
125Fh PID Function Enable A071 R/W
0 (disabling), 1 (enabling), 2 (enabling inverted-data
output)
-
1260h PID proportional gain A072 R/W 2 to 50 0.1
1261h PID integral time constant A073 R/W 0 to 36000 0.1 [sec.]
1262h PID derivative gain A074 R/W 0 to 10000 0.01 [sec.]
1263h PV scale conversion A075 R/W 1 to 9999 0.01
1264h PV source setting A076 R/W
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse train frequency input), 10
(operation result output)
-
1265h Reverse PID A077 R/W 00 (disabling), 01 (enabling) -
1266h PID output limiter A078 R/W 0 to 1000 0.1 [sec.]
1267h PID feed forward selection A079 R/W 0 (disabled), 1(O input), 2 (OI input), 3 (O2 input) -
1268h (Reserved) - R/W Inaccessible -
1269h AVR function select A081 R/W 0 (always on), 1 (always off), 2 (off during deceleration) -
126Ah AVR voltage select A082 R/W
200 V class: 0 (200)/1 (215)/2 (220)/3 (230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8 (440)/9 (460)/ 10
(480)
-
126Bh (Reserved) - R/W Inaccessible -
126Ch (Reserved) - R/W Inaccessible -
126Dh Operation mode selection A085 R/W
0 (normal operation), 1 (energy-saving operation), 2
(fuzzy operation)
-
126Eh Energy saving mode tuning A086 R/W 0 to 1000 0.1 [%]
126Fh to
1273h
(Reserved) - - Inaccessible -
1274h A092 (high) R/W
1275h
Acceleration (2) time
setting
A092 (low) R/W
1 to 360000 0.01 [sec.]
1276h A093 (high) R/W
1277h
Deceleration (2) time
setting
A093 (low) R/W
1 to 360000 0.01 [sec.]
1278h
Select method to switch to
Acc2/Dec2 profile
A094 R/W 0 (switching by 2CH terminal), 1 (switching by setting) -
1279h A095 (high) R/W
127Ah
Acc1 to Acc2 frequency
transition point
A095 (low) R/W
0 to 40000 0.01 [Hz]
127Bh A096 (high) R/W
127Ch
Dec1 to Dec2 frequency
transition point
A096 (low) R/W
0 to 40000 0.01 [Hz]
127Dh
Acceleration curve
selection
A097 R/W
0 (linear), 1 (S curve), 2 (U curve), 3 (inverted-U
curve), 4 (EL-S curve)
-
127Eh Deceleration curve setting A098 R/W
0 (linear), 1 (S curve), 2 (U curve), 3 (inverted-U
curve), 4 (EL-S curve)
-
127Fh (Reserved) - - Inaccessible -
1280h (Reserved) - - Inaccessible -
1281h A101 (high) R/W
1282h
[OI]-[L] input active range
start frequency
A101 (low) R/W
0 to 40000 0.01 [Hz]
1283h A102 (high) R/W
1284h
[OI]-[L] input active range
end frequency
A102 (low) R/W
0 to 40000 0.01 [Hz]
1285h
[OI]-[L] input active range
start current
A103 R/W 0 to "[OI]-[L] input active range end current" 1 [%]
1286h
[OI]-[L] input active range
end current
A104 R/W "[OI]-[L] input active range start current" to 100 1 [%]
1287h
[OI]-[L] input start
frequency enable
A105 R/W 0 (external start frequency), 1 (0 Hz) -
1288h to
128Ch
(Reserved) - - Inaccessible -
128Dh A111 (high) R/W
128Eh
[O2]-[L] input active range
start frequency
A111 (low) R/W
-40000 to 40000 0.01 [Hz]
128Fh A112 (high) R/W
1290h
[O2]-[L] input active range
end frequency
A112 (low) R/W
-40000 to 40000 0.01 [Hz]
1291h
[O2]-[L] input active range
start voltage
A113 R/W -100 to "[O2]-[L] input active range end voltage" 1 [%]
1292h
[O2]-[L] input active range
end voltage
A114 R/W "[O2]-[L] input active range start voltage" to 100 1 [%]
1293h to
12A4h
(Reserved) - - Inaccessible -
12A5h
Acceleration curve
constants setting
A131 R/W 1 (smallest swelling) to 10 (largest swelling) -
12A6h
Deceleration curve
constants setting
A132 R/W 1 (smallest swelling) to 10 (largest swelling) -
12A7h to
12AEh
(Reserved) - - Inaccessible -
12AFh
Operation-target frequency
selection 1
A141 R/W
0 (digital operator), 1 (keypad potentiometer), 2 (input
via O), 3 (input via OI), 4 (external communication), 5
(option 1), 6 (option 2), 7 (pulse train frequency input)
-