Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 4 Explanation of Functions
4 - 162
(viii) List of registers (3rd control settings)
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
3103h F302 (high) R/W
3104h
Acceleration (1) time setting, 3rd
motor
F302 (low) R/W
1 to 360000 0.01 [sec.]
3105h F303 (high) R/W
3106h
Deceleration (1) time setting, 3rd
motor
F303 (low) R/W
1 to 360000 0.01 [sec.]
3107h to
3202h
(Reserved) - - Inaccessible -
(ix) List of registers (3rd control setting)
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
3203h
Base frequency setting, 3rd
motor
A303 R/W 30 to "maximum frequency, 3rd motor" 1 [Hz]
3204h
Maximum frequency setting, 3rd
motor
A304 R/W 30 to 400 1 [Hz]
3205h to
3215h
(Reserved) - - Inaccessible -
3216h A320 (high) R/W
3217h
Multispeed frequency setting, 3rd
motor
A320 (low) R/W
0 or "start frequency" to "maximum frequency, 3rd
motor"
0.01 [Hz]
3218h to
323Bh
(Reserved) - - Inaccessible -
323Ch
Manual torque boost value, 3rd
motor
A342 R/W 0 to 200 0.1 [%]
323Dh
Manual torque boost frequency
adjustment, 3rd motor
A343 R/W 0 to 500 0.1 [%]
323Eh
V/F characteristic curve
selection, 3rd motor
A344 R/W 0 (VC), 1(VP) -
323Fh to
326Ch
(Reserved) - - Inaccessible -
326Dh A392 (high) R/W
326Eh
Acceleration (2) time setting, 3rd
motor
A392 (low) R/W
1 to 360000 0.01 [sec.]
326Fh A393 (high) R/W
3270h
Deceleration (2) time setting, 3rd
motor
A393 (low) R/W
1 to 360000 0.01 [sec.]
3271h to
330B
(Reserved) - - Inaccessible -
330Ch
Electronic thermal setting
(calculated within the inverter
from current output), 3rd motor
b312 R/W 200 to 1000 0.1 [%]
330Dh
Electronic thermal characteristic,
3rd motor
b313 R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free setting)
-
330Eh to
3506h
(Reserved) - - Inaccessible -
3507h
Motor stabilization constant, 3rd
motor
H306 R/W 0 to 255 1
3508h to (Reserved) - - Inaccessible -