Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 8 List of Data Settings
8 - 7
Default
Code Function name Monitored data or setting
_FF _FEF _FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
b034 Run/power-on warning time 0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr) 0.
¯ {
4-64
b035 Rotational direction restriction
00 (enabling both forward and reverse rotations), 01 (enabling
only forward rotation), 02 (enabling only reverse rotation)
00
¯ ¯
4-7
b036 Reduced voltage start selection
0 (minimum reduced voltage start time) to 255 (maximum
reduced voltage start time)
6
¯ {
4-42
b037 Function code display restriction
00 (full display), 01 (function-specific display), 02 (user setting),
03 (data comparison display), 04 (basic display)
04
¯ {
4-76
b038 Initial-screen selection
00 (screen displayed when the STR key was pressed last), 01
(d001), 02 (d002), 03 (d003), 04 (d007), 05 (F001)
01
¯ {
4-78
Others
b039
Automatic user-parameter
setting function enable
00 (disabling), 01 (enabling) 00
¯ {
4-79
b040 Torque limit selection
00 (quadrant-specific setting), 01 (switching by terminal), 02
(analog input), 03 (option 1), 04 (option 2)
00
¯ {
b041
Torque limit (1) (forward-driving
in 4-quadrant mode)
0. to 200. (%), no (disabling torque limitation) 150.
¯ {
b042
Torque limit (2)
(reverse-regenerating in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation) 150.
¯ {
b043
Torque limit (3) (reverse-driving
in 4-quadrant mode)
0. to 200. (%), no (disabling torque limitation) 150.
¯ {
b044
Torque limit (4)
(forward-regenerating in
4-quadrant mode)
0. to 200. (%), no (disabling torque limitation) 150.
¯ {
4-92
b045 Torque limit LADSTOP enable 00 (disabling), 01 (enabling) 00
¯ {
4-94
Torque limitation
b046 Reverse Run protection enable 00 (disabling), 01 (enabling) 00
¯ {
4-93
b050
Controller deceleration and stop
on power loss
00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage
constant control, with resume), 03 ( without resume)
00
¯ ¯
b051
DC bus voltage trigger level
during power loss
0.0 to 999.9, 1000. (V) 0.0
¯ ¯
b052
Over-voltage threshold during
power loss
0.0 to 999.9, 1000. (V) 0.0
¯ ¯
b053
Deceleration time setting during
power loss
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 1.00
¯ ¯
b054
Initial output frequency decrease
during power loss
0.00 to 10.00 (Hz) 0.00
¯ ¯
b055
Proportional gain setting for
nonstop operation at power loss
0.00 to 2.55 0.20
{ {
Non-stop operation at momentary power
failure
b056
Integral time setting for nonstop
operation at power loss
0.000 to 9.999 /10.00 to 65.53 (s) 0.100
{ {
4-83
b060
Maximum-limit level of window
comparators O
0. to 100. (lower limit : b061 + b062 / 2) (%) 100
{ {
b061
Minimum-limit level of window
comparators O
0. to 100. (lower limit : b060 - b062 / 2) (%) 0
{ {
b062
Hysteresis width of window
comparators O
0. to 10. (lower limit : b061 - b062 / 2) (%) 0
{ {
b063
Maximum-limit level of window
comparators OI
0. to 100. (lower limit : b064 + b066 / 2) (%) 100
{ {
b064
Minimum-limit level of window
comparators OI
0. to 100. (lower limit : b063 - b066 / 2) (%) 0
{ {
b065
Hysteresis width of window
comparators OI
0. to 10. (lower limit : b063 - b064 / 2) (%) 0
{ {
b066
Maximum-limit level of window
comparators OI
-100. to 100. (lower limit : b067 + b068 / 2) (%) 100
{ {
b067
Minimum-limit level of window
comparators O/OI/O2
-100. to 100. (lower limit : b066 - b068 / 2) (%) 0
{ {
b068
Hysteresis width of window
comparators O/OI/O2
0. to 10. (lower limit : b066 - b067 / 2) (%) 0
{ {
b070
Operation level at O
disconnection
0. to 100. (%) or "no" (ignore) no
¯ {
b071
Operation level at OI
disconnection
0. to 100. (%) or "no" (ignore) no
¯ {
Window comparator
b072
Operation level at O2
disconnection
-100. to 100. (%) or "no" (ignore) no
¯ {
4-71