Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 3 Operation
3 - 10
3.3 How To Make a Test Run
This section describes how to make a test run of the inverter that is wired and connected to external
devices in a general way as shown below.
For the detailed method of using the digital operator, see Section 3.2, "How To Operate the Digital
Operator."
(1) When entering operation and frequency-setting commands from the digital operator:
(The operating procedure below is common to the standard and optional digital operators.)
(Operating procedure)
1) Confirm that all wirings are correct.
2) Turn on the earth-leakage breaker (ELB) to supply power to the inverter.
(The POWER lamp [red LED] of the digital operator goes on.)
* When using an inverter with the factory setting, proceed to step 5).
3) Select the digital operator as the operating device via the frequency source setting function.
- Display the function code "A001" on the monitor screen, and then press the key once.
(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to [02], and then press the
key once to specify the digital operator as the operating device to input frequency-setting
commands.
(The display reverts to [A001].)
4) Select the digital operator as the operating device by the run command source setting function.
- Display the function code "A002" on the monitor screen, and then press the key once.
(The monitor shows a 2-digit numeric value.)
- Use the and/or key to change the displayed numeric value to "02", and then press the
key once to specify the digital operator as the operating device to input operation commands.
(The display reverts to [A002]. The operating device indicator lamp above the [RUN] key goes on.)
5) Set the output frequency.
- Display the function code "F001" on the monitor screen, and then press the key once.
(The monitor shows a preset output frequency. With the factory setting, [0 Hz] is shown.)
- Use the and/or key to change the displayed numeric value to the desired output frequency,
and then press the key once to determine the frequency.
(The display reverts to [F001].)
6) Set the operation direction of the motor.
- Display the function code "F004" on the monitor screen, and then press the key once.
(The monitor shows "00" or "01".)
G
Type-D grounding (200 V class model)
Type-C grounding (400 V class model)
DC reactor
Moto
r
U
V
W
PD
P
RB
N
A
L0
A
L1
A
L2
11
CM2
15
SP
SN
RP
SN
Braking unit
A
larm output contacts
A
MI
A
M
L
O2
OI
O
H
P24
PLC
CM1
TH
FM
1
8
FW
R
S
T
R
S
T
3-phase
power supply
ELB
Digital operator
FUNC
FUNC
STR
STR
1
2
FUNC
1
2
STR
1
2
FUNC
Default jumper position for sinking type inputs
(Altanatively, CM1-PLC for souricing tiype)