Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 8 List of Data Settings
8 - 2
Code Function name Monitored data or setting Default
Setting during
operation
(allowed or not)
Change during
operation
(allowed or not)
Page
d025 User monitor 0 -2147483647 to 2147483647 (upper 4 digits including “-“)
d026 User monitor 1 -2147483647 to 2147483647 (upper 4 digits including “-“)
d027 User monitor 2 -2147483647 to 2147483647 (upper 4 digits including “-“)
4-5
d028 Pulse counter 0 to 2147483647 (upper 4 digits)
4-5
d029 Position setting monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
4-5
d030 Position feedback monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
4-5
d080 Trip Counter 0. to 9999., 1000 to 6553 (10000 to 65530) (times)
4-5
d081
Trip monitoring 1 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
d082
Trip monitoring 2 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
d083
Trip monitoring 3 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
d084
Trip monitoring 4 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
d085
Trip monitoring 5 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
d086
Trip monitoring 6 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)
4-6
d090 Programming error monitoring Warning code
4-6
d102 DC voltage monitoring 0.0 to 999.9 (V)
4-6
d103 BRD load factor monitoring 0.0 to 100.0 (%)
4-6
d104 Electronic thermal overload monitoring 0.0 to 100.0 (%)
4-6
8.3 Function Mode
Default
Code Function name Monitored data or setting
_
FF
_
FEF
_
FUF
Setting during
operation
(allowed or
not)
Change during
operation
(allowed or
not)
Page
F001
Output frequency setting 0.0, "start frequency" to "maximum frequency" (or maximum frequency,
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.00
{ {
4-7
F002 Acceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F202 Acceleration (1) time setting, 2nd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F302 Acceleration (1) time setting, 3rd
motor
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F003 Deceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F203 Deceleration time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F303 Deceleration time setting, 3rd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
{ {
4-10
F004 Keypad Run key routing 00 (forward rotation), 01 (reverse rotation) 00
¯ ¯