Hitachi SJ700-2 Marine Battery User Manual


 
Chapter 4 Explanation of Functions
4 - 24
4.2.20 Frequency upper limit setting
The frequency upper limit setting function allows you to place
upper and lower limits on the inverter output frequency.
This function restricts the input of frequency commands that
specify any frequencies outside the upper and lower limits.
Always set the upper limit before setting the lower limit. Also, be sure to keep the frequency upper limit
(A061/A261) larger than the frequency lower limit (A062/A262).
Be sure that upper limit/lower limit does not exceed Maximum frequency (A004/A204/A304).
Be sure to set output frequency (F001) and multiple speed 1 to 15 (A021 to A035) in between uppelimit
and lower limit.
If 0 Hz is set for the frequency upper and lower limits, they will not operate.
The frequency limit setting function is disabled when the 3rd control system is selected.
Item Function code Range of data Description
Frequency upper
limit setting
A061/A261
0.00 or a frequency more than the
frequency lower limit setting up to the
maximum frequency (Hz)
Setting of the upper limit of the
output frequency
Frequency lower
limit setting
A062/A262
0.00 or a frequency not less than the
starting frequency up to the frequency
upper limit setting (Hz)
Setting of the lower limit of the
output frequency
(1) When the O-L or OI-L terminal is used:
(2) When the O2-L terminal is used:
If the frequency lower limit is used with the frequency command input via the O2-L terminal, the motor
speed with 0 V input will be fixed to the frequency setting of the frequency lower limit (A062) for forward
rotation or the frequency setting of the frequency lower limit (A062) for reverse rotation as shown below.
(a) When operation commands are input via the control circuit terminal block (A002: 01)
Terminal Motor speed with 0 V input via O2 terminal
FW(ON) Frequency setting by A062 for forward rotation
RV(ON) Frequency setting by A062 for reverse rotation
(b) When operation commands are input from the digital operator (A002: 02)
F004 Motor speed with 0 V input via O2 terminal
00 Frequency setting by A062 for forward rotation
01 Frequency setting by A062 for reverse rotation
A061/A261: /Frequency upper limit setting,
1st/2nd motors
A062/A262: Frequency lower limit setting,
1st/2nd motors
Related code
A062
A061
Output frequency (Hz)
Frequency command
0 V
4 mA
10 V
20 mA
Maximum frequency
A004/A204
If 0 V or 4 mA is input as the frequency command
when a frequency lower limit has been set for the
frequency lower limit setting (A062), the inverter
will output the set frequency.
A062
A061
A004
/
A204
A062
A061
10 V
-10 V
Maximum frequency
A004/A204
Reverse rotation Forward rotation
Maximum frequency