Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
7-35
Rosemount 5300 Series
Device Status Device Status messages that may appear on the Integral Display, on the 375
Field Communicator, or in RMM are shown in Table 7-4:
Table 7-4. Device status.
Message Description Action
Running Boot Software The application software could not be
started.
Contact Emerson Process
Management Service Department.
Device Warning A device warning is active. See Warning Messages for details.
Device Error A device error is active. See Error Messages for details.
Sim Mode 0 Active The simulation mode is active. Turn off the simulation mode in RRM,
select Tools, Simulation Mode, and
click the Stop button.
Advanced Simulation Mode
Active
The advanced simulation mode is
active.
To turn off the Advanced Simulation
mode, set Holding Register 3600=0
(see “Viewing Input and Holding
Registers” on page 7-27).
Interface Invalid The interface measurement is invalid. Check the Error Messages, Warning
Messages, and the Interface Status
for details.
Invalid Measurement The level measurement is invalid. Check Error Messages, Warning
Messages, and Measurement Status
for details.
User Register Area Write
Protected
The configuration registers are write
protected.
Use the Lock/Unlock function to turn
off the write protection (see “Write
Protecting a Transmitter” on
page 7-26).
Write Protected Jumper Set Write protection jumper on the display
is enabled.
Remove the write protection jumper.
Factory Settings Used The factory default configuration is
used.
The transmitter has lost its calibration.
Contact Emerson Process
Management Service Department.
Probe missing Probe is not detected. Check that the probe is correctly
mounted. Check the connection
between probe and transmitter head.