Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
B-3
Rosemount 5300 Series
EUROPEAN ATEX
DIRECTIVE
INFORMATION
Intrinsic Safety The Rosemount 5300 Series Guided Wave Radar Level Transmitter that has
the following label attached has been certified to comply with Directive
94/9/EC of the European Parliament and the Council as published in the
Official Journal of the European Communities No. L 100/1 on 19-April-1994.
Figure B-1. Approval Label
ATEX HART model
I1 The following information is provided as part of the label of the
transmitter:
Name and address of the manufacturer (Rosemount).
CE Conformity Marking
Complete model number
The serial number of the device
Year of construction
Marking for explosion protection:
EEx ia IIC T4 (-50 °C
T
a
+70 °C)
(1)
4-20 mA/HART model: U
i
=30 V, I
i
=130 mA, P
i
=1.0 W, C
i
=7.26 nF, L
i
=0.
Nemko ATEX certificate number: Nemko 04ATEX1073X
Installation Drawing: 9240 030-938
Special Conditions for Safe Use (X):
The intrinsically safe circuits do not withstand the 500V AC test as specified in
EN 50020 clause 6.4.12.
Probes covered with plastic and/or with plastic discs will have a
non-conducting area that exceeds the maximum permissible areas for Group
IIC and Category II 1G according to EN 50284 clause 4.4.3 (4 cm
2
).
Therefore, when the probe is used in a potentially explosive atmosphere,
appropriate measures must be taken to prevent electrostatic discharge.
Impact and friction hazards need then to be considered according to EN
50284 clause 4.3.1 when the transmitter exposed to the exterior atmosphere
of the tank is made with light metal alloys and used in category II 1 G.
(1) Other temperature restrictions may apply, please refer to “Specifications” on page A-1.