Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
E-6
4. Using loop test, enter the mA value representing the low alarm mode.
Verify that the analog output current is correct using the reference meter.
This step tests for possible quiescent current related failures.
AMS: Select Configure / Setup, Analog Output from the menu. Click
Loop Test... Select Other and enter the mA value representing the low
Analog Output Level and follow the instructions. Click OK to save
changes. Verify that the output current is correct.
Select End to stop loop test. Verify that the Current output is restored to
the original mode.
5. Perform a two-point calibration check of the transmitter by applying level
to two points on the probe within the measuring range. Verify that the
current output corresponds to the level input values using a known
reference measurement.
This step verifies that the analog output is correct in the operating range
and that the Primary Variable is properly configured.
Note that the applied level has to be between the Upper and Lower
Range values, otherwise the transmitter enters alarm mode. If the
applied level is outside the Maximum Measuring Range, the level
reading accuracy may be reduced. For best performance, use the
4-20 mA range points as calibration points. See Figure E-1 on page E-2.
6. Enable write protection.
AMS: Select Device Diagnostics / Tools from the menu, click Write
Protect... and follow the instructions. (Note that the password cannot be
written with letters.)
7. Restore the loop to full operation.
8. Remove the bypass from the safety PLC or otherwise restore normal
operation.
9. Document the test results for future reference.