Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
7-41
Rosemount 5300 Series
Analog Output Status Analog Output Status messages that may appear on the Integral Display, on
the 375 Handheld Communicator, or in RRM are shown in Table 7-10:
Table 7-10. Analog Output
status.
Message Description Action
Not connected Analog output hardware is not
connected.
Alarm Mode The analog output is in Alarm Mode. Check Error and Warning Messages
to find the reason for the Alarm.
Saturated The analog output signal value is
saturated, i.e. equal to the saturation
value.
No action needed.
Multidrop The transmitter is in Multidrop Mode.
The analog output is fixed at 4 mA.
This is the normal setting when a
device is used in Multidrop
configuration.
Fixed Current mode The analog output is in fixed current
mode.
This mode is used when calibrating
the Analog Output channel.
PV out of Limits The Primary variable is out of range. Check the Upper and Lower Range
Value
Span Too Small The configured span is too small. Check the Upper and Lower Range
Value.
Invalid Limits The given Upper and Lower Sensor
Limits are invalid.
Check that the difference between the
Upper and Lower Sensor Limits is
greater than the Minimum Span.