Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
B-19
Rosemount 5300 Series
Figure B-21. Approval Label
IECEx FISCO model
IG Intrinsically Safe
Ex ia IIC T4 (T
amb
-50 °C to +60 °C).
IECEx NEM 06.0001X.
FISCO: U
i
=17.5 V, I
i
=380 mA, P
i
=5.32 W, C
i
=0 nF,
L
i
=0 mH.
Installation Drawing: 9240 030-938.
Conditions of Certification
The intrinsically safe circuits do not withstand the 500V AC test as specified in
EN 50020 clause 6.4.12.
Probes covered with plastic and/or with plastic discs will have a
non-conducting area that exceeds the maximum permissible area for Group
IIC accoring to IEC 60079-01 clause 7.3: 20 cm
2
for Zone 1 and 4 cm
2
for
Zone 0. Therefore, when the probe is used in a potentially explosive
atmosphere, appropriate measures must be taken to prevent electrostatic
discharge.
Impact and friction hazards need then to be considered according to IEC
60079-0 clause 8.1.2 when the transmitter exposed to the exterior
atmosphere of the tank is made with light metal alloys and used in Zone 0.