Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-22
Geometry
6. Geometry
HART command: [2, 1, 3].
F
OUNDATION Fieldbus parameter:
TRANSDUCER 1100>GEOM_TANK_HEIGHT
TRANSDUCER 1100>MOUNTING_TYPE
TRANSDUCER 1100>PIPE_DIAMETER
TRANSDUCER 1100>NOZZLE_HEIGHT
Tank Height is the distance from the Upper Reference Point to the Lower
Reference Point (see Figure 5-1 on page 5-4 and Figure 5-2 on page 5-4).
The Upper Reference Point is located at the bottom part of the threaded
adapter, or at the underside of the welded flange.
Make sure the Tank Height is as accurate as possible, since a Tank Height
error results in a corresponding Level value offset error.
When specifying the Tank Height, keep in mind that this value is used for all
level and volume measurements performed by the Rosemount 5300 Series
transmitter.
The Tank Height must be set in linear (level) units, such as feet or meters,
regardless of primary variable assignment.
Select the Mounting Type used.
Select Inner Diameter if using pipe, chamber or nozzle.
Type Nozzle Height if using nozzle.