Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
3-19
Rosemount 5300 Series
Shortening the Probe NOTE!
HTHP Coaxial and PTFE probes must not be shortened.
Flexible Twin/Single Lead
Rigid Single Lead
1. Cut the Single Lead probe to the desired length. The minimum probe
length is 15.7 in. (400 mm).
2. If a centering disc is used, follow the instructions on page 3-26.
3. Update the transmitter configuration to the new probe length, see “Tank
and Probe Geometry“ on page 5-4 and “Probe“ on page 5-21.
Allen
screws
Minimum:
1.6 in./
40 mm
Spacer
Cut
1. Mark off the required probe length. Add at least
1.6 in. (40 mm) to the required probe length to be
inserted into the weight.
2. Loosen the Allen screws.
3. Slide the weight upwards as much as needed in
order to cut the probe.
4. Cut the probe. If necessary, remove a spacer to make
room for the weight.
5. Slide the weight down to the required cable length.
6. Tighten the screws. Required torque:
M6: 7 Nm
M8: 15 Nm
M10: 25 Nm
7. Update the transmitter configuration to the new probe
length, see “Tank and Probe Geometry“ on page 5-4
and “Probe“ on page 5-21.
If the weight was removed from the cables when cutting,
make sure that at least 1.6 in. (40 mm) of the cable is
inserted when the weight is replaced.
NOTE!
If the screws are not tightened according to the required
torque, the weight may fall off. This is especially
important for solid applications with high tensile loads on
the probe.