Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
4-8
FOUNDATION FIELDBUS
Power Requirements Terminals in the transmitter housing provide connections for signal cables.
The Rosemount 5300 transmitter is powered over F
OUNDATION Fieldbus with
standard fielbus power supplies. The transmitter operates with the following
power supplies:
Connecting the
Transmitter
To connect the transmitter:
1. Make sure the power supply is switched off.
2. Remove the terminal block cover.
3. Pull the cable through the cable gland/conduit. Install wiring with a drip
loop. The bottom of the loop must be lower than the cable/conduit entry.
4. Connect wires according to Figure 4-9 for non-intrinsically safe power
supplies, and according to Figure 4-10 for intrinsically safe power
supplies.
5. Use the enclosed metal plug to seal any unused port.
6. Mount the cover and tighten the cable gland making sure the cover is
secure to meet explosion-proof requirements.
7. For ATEX, IECEx and NEPSI installations, lock the cover with the
Locking Screw .
8. Connect the power supply.
NOTE!
Use PTFE tape or other sealant at the NPT threads in the Cable Entries.
Approval Type Power Supply (Vdc)
IS 9 - 30
Explosion-Proof/Flameproof 16 - 32
None 9 - 32
FISCO; IS 9 - 17.5