Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-16
Installing the RRM
Software for
FOUNDATION Fieldbus
To install the Rosemount Radar Master for FOUNDATION Fieldbus
communication:
1. Start by installing the National Instruments Communication Manager
software. See National Instruments manual (Getting started with your
PCMCIA-FBUS and the NI-FBUS™ software) for more information.
2. Insert the RRM installation CD into your CD-ROM drive.
3. If the installation program is not automatically started, choose Run from
the Windows Start bar.
4. Type D:\RRM\Setup.exe where D is the CD-ROM drive.
5. Follow the instructions on the screen.
6. Make sure that F
OUNDATION Fieldbus is chosen as default protocol.
Getting Started
1. Before starting RRM make sure that appropriate settings are made with
the National Instruments Interface Configuration Utility:
If only Rosemount Radar Master is connected to the bus:
Device address=Fixed
Device Type=Link Master Device
Usage=NI-FBUS
If other host systems are connected to the bus:
Device address=Visitor
Device Type=Basic Device
Usage=NI-FBUS