Emerson Process Management 5300 Marine RADAR User Manual


 
Reference Manual
00809-0100-4530, Rev BA
July 2009
J-3
Rosemount 5300 Series
SIMULATION To support testing, you can either change the mode of the block to manual
and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and
its status. In both cases, you must first set the ENABLE jumper on the field
device.
NOTE!
All fieldbus instruments have a simulation jumper. As a safety measure, the
jumper has to be reset every time there is a power interruption. This measure
is to prevent devices that went through simulation in the staging process from
being installed with simulation enabled.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status.
LO_PRI 29 None The priority of the LO alarm.
LOW_CUT 17 % If percentage value of transducer input fails below this, PV = 0.
MODE_BLK 05 None The actual, target, permitted, and normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT 08 EU of OUT_SCALE The block output value and status.
OUT_D 37 None Discrete output to indicate a selected alarm condition.
OUT_SCALE 11 None The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with OUT.
PV 07 EU of XD_SCALE The process variable used in block execution.
PV_FTIME 18 Seconds The time constant of the first-order PV filter. It is the time required for a 63% change
in the IN value.
SIMULATE 09 None A group of data that contains the current transducer value and status, the simulated
transducer value and status, and the enable/disable bit.
STRATEGY 03 None The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.
ST_REV 01 None The revision level of the static data associated with the function block. The revision
value will be incremented each time a static parameter value in the block is
changed.
TAG_DESC 02 None The user description of the intended application of the block.
UPDATE_EVT 20 None This alert is generated by any change to the static data.
VAR_INDEX 39 % of OUT Range The average absolute error between the PV and its previous mean value over that
evaluation time defined by VAR_SCAN.
VAR_SCAN 40 Seconds The time over which the VAR_INDEX is evaluated.
XD_SCALE 10 None The high and low scale values, engineering units code, and number of digits to the
right of the decimal point associated with the channel input value.
Parameter
Index
Number
Units Description