5-39
5-4-5 Parameter Constant Reading and Writing
The following tables show the SYSDRIVE 3G3FV-series Inverter parameter constant numbers and the
corresponding register numbers. Write and read the various parameter constants with 1 as the mini-
mum setting unit. Negative numbers are expressed as twos complement. If the setting unit is in hexade-
cimal, there is no need to convert it.
When writing data in parameter constants, be sure to send an enter command to enable the written
data. Unless the enter command is transmitted, the data will not be enabled and the Inverter may not
start.
H Constants for Initialize Mode
Constant Name Regis- Setting Setting Default Chang
Control mode setting
ter No. unit range setting es dur-
ing op-
eration
V/f
control
V/f with
PG
Open
loop
vector
Flux
vector
A1-00 Display Language 0100 1 0, 1 1 Yes Yes Yes Yes Yes
A1-01 Access Level 0101 1 0 to 4 2 Yes Yes Yes Yes Yes
A1-02 Select Control
Method
0102 1 0 to 3 2 No Yes Yes Yes Yes
A1-03 Initialize 0103 1 0 to 3,330 0 No Yes Yes Yes Yes
A1-04 Password 0104 1 0 to 9,999 0 No Yes Yes Yes Yes
A1-05 Setting the Password 0105 1 0 to 9,999 0 No Yes Yes Yes Yes
H Parameter Constants for Program Mode
D Application (b) Parameter Constants
Constant Name Regis- Setting Setting Default Chang
Control mode setting
ter No. unit range setting es dur-
ing op-
eration
V/f
control
V/f with
PG
Open
loop
vector
Flux
vector
b1-01 Frequency Reference
Selection
0180 1 0 to 3 1 No Yes Yes Yes Yes
b1-02 Run Source Selection 0181 1 0 to 3 1 No Yes Yes Yes Yes
b1-03 Stopping Method
Selection
0182 1 0 to 3 0 No Yes Yes Yes Yes
b1-04 Disabling Reverse
Operation
0183 1 0. 1 0 No Yes Yes Yes Yes
b1-05 Operation Selection
for Minimum
Frequency (E1-09 or
less)
0184 1 0 to 3 0 No No No No Yes
b1-06 Setting Control Input
Responsiveness
0185 1 0, 1 1 No Yes Yes Yes Yes
b1-07 Operation Selection
After Switching to
Remote Mode
0186 1 0, 1 0 No Yes Yes Yes Yes
b2-01 Excitation level (DC
injection starting
frequency)
0187 0.1 0.0 to 10.0 0.5 No Yes Yes Yes Yes
b2-02 DC injection braking
current
0188 1 0 to 100 50 No Yes Yes Yes No
b2-03 DC injection braking
time at start.
0189 0.01 0.00 to 10.00 0.00 No Yes Yes Yes Yes
CompoBus/D Communications Card Operations Chapter 5