H Connecting Terminating Resistors
Terminating resistors must be connected at each end of the trunk line. Use the methods described here
to connect the Terminating Resistors.
D T-branch Tap Terminating Resistor
A Terminating Resistor is included with the T-branch Tap. Insert the Terminating Resistor into the T-
branch Tap as shown in the following diagram. The Terminating Resistor can face in either direction.
D Terminal-block Terminating Resistor
20
41 max.
20 max.
21 max.
A Terminating Resistor is built into the Terminal-block Terminating Resistor. To connect the cable to the
Terminating Resistor, attach standard M3 crimp terminals to the signal wires and securely screw the
terminals to the Terminal-block Terminating Resistor. Tighten to a torque of 0.5 N@m.
6.0 mm max. 6.0 mm max.
Note To avoid damaging the cable or breaking wires, do not pull on the cable or bend it too sharply when
connecting it to the terminal block. Also, never place heavy objects on top of the cable.