Omron 3G3FV-PDRT1-SIN Marine Radio User Manual


 
6-5
6-2 Message Communications Errors
H Explicit Message Errors
If an explicit message is sent, but communications do not end normally, one of the following error codes
will be returned with service code 94. Check the meaning of the error message, and either correct the
message or adjust the timing of the message.
Error
Code
Meaning Countermeasures
0000 Normal end response. ---
08FF The requested service does not exist. Correct the service code and send the data
again.
09FF An invalid attribute was detected. Check and correct the attribute values, and
send the data again.
0CFF The requested service cannot be executed in
the current object mode or status.
Stop the Inverter and send the data again.
0EFF A request has been sent to change an attribute
that cannot be changed.
Check and correct the service code and
attribute values, and send the data again.
13FF There is insufficient data to execute the service. Correct the data size and send the data again.
14FF The attribute for the service does not exist. Check and correct the service code and
attribute values, and send the data again.
15FF These is too much data to execute the service. Correct the data size and send the data again.
16FF The specified object does not exist. Check and correct the class and instance
values, and send the data again.
20FF The parameters are invalid or the data is
outside the range for the requested service.
Check and correct the data setting range, send
the data again.
1FFF Manufacturer fault code. Stop the Inverter and send the data again.
Check and correct the data setting range, send
the data again.
Communications Errors Chapter 6