Omron 3G3FV-PDRT1-SIN Marine Radio User Manual


 
5-13
5-2-3 SYSMAC CV-series Message Transmission
H Using CMND(194)
With CV-series PCs, CMND(194) is used to send explicit messages. To send an explicit message, it is
necessary to place FINS command 2801 in front and to send the command to the Master Unit. The
Master Unit that receives the command converts the command data to an explicit message and trans-
fers it to the destination node. When sending an explicit message, it is not possible to directly specify the
destination node with CMND(194).
(194)
CMND S D C
D S: Beginning Command Storage Word
Specify the beginning word address for the command data transferred to the CompoBus/D Master Unit.
Preset the data to be transferred in consecutive words as shown in the following table.
Word address
Bits
15 to 8 7 to 0
S Command data (Set explicit message FINS command 2801.)
S+1 Node of Slave or Master for transmission
Address: 0 to 3F hex (0 to 63)
Explicit message service code
Write: 10 Read: 0E
S+2 Class ID code (Set DeviceNet class code for relevant function.)
Set within 0001 to 002A (hex) with Inverters CompoBus/D Communications Card.
S+3 Instance ID code (Set DeviceNet instance code for relevant function.)
Set within 0001 to 0003 (hex) with Inverters CompoBus/D Communications Card.
S+4 Attribute ID code
(Set DeviceNet attribute code for relevant
function.)
Attached data (for writing)
--- Attached data (for writing)
D D: Beginning Response Storage Word
Specify the beginning word address of the area for storing responses to messages.
CompoBus/D Communications Card Operations Chapter 5