Instance SizeWriteReadDefaultSetting
range
ContentNameAttribute
01
09 Current Actual Can be referenced in hexadecimal with the
output current monitor (U103) minimum
unit as 0.1 A.
Setting the attribute 17 current scale
enables a multiplication factor to be set.
--- 0000 Yes No Word
0F Power Actual Can be referenced in hexadecimal with the
output power monitor (U108) minimum
unit as 1 W.
Setting the attribute 1A power scale
enables a multiplication factor to be set.
--- 0000 Yes No Word
10 Input Voltage Can be referenced in hexadecimal with the
input voltage setting (E101) minimum unit
as 1 V.
Setting the attribute 1B voltage scale
enables a multiplication factor to be set.
--- 0000 Yes No Word
11 Output Voltage Can be referenced in hexadecimal with the
output voltage monitor (U106) minimum
unit as 1 V.
Setting the attribute 1B voltage scale
enables a multiplication factor to be set.
--- 0000 Yes No Word
12 Accel Time
Can be set and read in hexadecimal with
the acceleration time 1 (C101) and
deceleration time 1 (C102) minimum unit
as 1 ms.
Depending on the acceleration/
0.0 to
6,000.0 ×
10
3
ms
(0.00 to
600.00 ×
3
2710
Hex
(10.0 s)
Yes Yes Word
13 Decel Time
Depending on the acceleration/
deceleration time unit (C101) setting,
numbers below 100 ms or 10 ms are
truncated.
Setting the attribute 1C time scale enables
a multiplication factor to be set.
10
3
ms)
2710
Hex
(10.0 s)
Yes Yes Word
14 Low Speed Limit
(See note 1 and
3.)
Can be set and read in hexadecimal with
the frequency reference lower limit (d202)
and the frequency reference upper limit
(d201) minimum unit as 1 ms.
The minimum unit can be set by the
frequency reference setting and display
0 to
109% of
maximum
frequency
0000 Yes Yes Word
15 High Speed Limit
(See note 1 and
3.)
units (o103).
o103= 2 to 39: 1 r/min
o103= Other than above: 0.1% (Maximum
frequency: 100%)
Setting the attribute 16 speed scale
enables a multiplication factor to be set for
o103= 2 to 39: 1 r/min.
0 to 110%
of
maximum
frequency
0708
Hex
(1,800
r/min)
Yes Yes Word
16 Speed scale Speed data unit selection can be set and
read. The speed data unit value is
calculated as follows:
Unit = 1 [r/min] x 1/2
a
a: Speed scale set value
Set a negative value as its 2s
complement.
15 to 15
(F1 to 0F
hex)
00 Yes Yes Byte
17 Current scale Current data unit selection can be set and
read. The current data unit value is
calculated as follows:
Unit = 0.1 [A] x 1/2
b
b: Current scale set value
Set a negative value as its 2s
complement.
15 to 15
(F1 to 0F
hex)
00 Yes Yes Byte