D Output Terminal Status: Register Number 002A Hex
Bit Content
0 1: Terminal 9 and 10 short
1 1: Terminal 25 and 27 short
2 1: Terminal 26 and 27 short
3
Not used.
4
5
6
7 1: Terminal 18 and 20 short
8 to 15 Not used.
D Operating Status: Register Number 002B Hex
Bit Content
0 During RUN
1 Zero speed
2 Forward/reverse (1: Reverse operation)
3 During Fault Reset input
4 Frequency agree 1
5 Operation ready
6 Alarm
7 Fault
8 to 15 Not used.