5-18
H Object Details
Instance Attribute Name Content Setting
range
Default Read Write Size
00 01 Object Software
Revision
Indicates class 29 software
revisions. The revision value is
advanced whenever there is a
change.
--- 0001 Yes No Word
01
03 Forward/Stop 00: Stop
01: Forward operation
00, 01 00 Yes Yes Byte
04 Reverse/Stop 00: Stop
01: Reverse operation
00, 01 00 Yes Yes Byte
05 Net Control
Local/remote switch
Set note 1.
00: Operate by b1–02 setting.
01: Operate by CompoBus/D with
b1–02 set to “3.”
00, 01 00 Yes Yes Byte
06 State
Inverter status
03 hex: Inverter ready --- 03 Yes No Byte
07 During forward run 00: No Inverter output or operating
in reverse.
01: Forward operation or DC
braking
Turns ON even for DC braking
during reverse operation.
--- 00 Yes No Byte
08 During reverse run 00: No Inverter output or operating
in forward.
01: Operating in reverse (reverse
operation output status)
Becomes “00” with DC braking.
--- 00 Yes No Byte
09 Inverter Ready 00: Preparing
Initial processing/ not drive mode/
fault
01: Inverter ready
Inverter can receive run
command.
--- 00 Yes No Byte
0A Fault 00: Normal
01: Fault
--- 00 Yes No Byte
0B Warning (minor fault) 00: Normal
01: Warning (minor fault)
--- 00 Yes No Byte
0C Fault Reset 00: Normal status
01: Fault reset
00, 01 00 Yes Yes Byte
0D Fault code Indicates the contents of fault that
occur. (See the fault code list on
the following page.)
--- 0000 Yes No Word
0F Control From Net
Run signal input
status
See note 1.
00: Operating by b1–02 setting.
01: Operating by CompoBus/D.
--- 00 Yes No Byte
10 DeviceNet Fault
mode
See note 2.
02: Maker’s specifications --- 02 Yes No Byte
11 Force Fault/Trip
Communications
external fault input
00: Normal operation
01: Communications external fault
input (according to parameter F9 )
00, 01 00 Yes Yes Byte
12 Force Status
Communications
external fault input
status
00: Normal status
01: Communications external fault
detected. (Inverter stopped with
fault detection.)
--- 00 Yes No Byte
Note 1. The Net Control and Control From Net functions are applicable for Inverter software versions
S1042 and later. Cannot be changed during running. Check the version with the Inverter mon-
itor function U1–14. If the software version is S1040, set b1–02 to “3.”
CompoBus/D Communications Card Operations Chapter 5