8. Connect a Configurator to the Network.
9. Turn ON the power supply to all nodes.
10. Switch the PC to PROGRAM mode.
11. Get the device list and create the master parameters with the Configurator.
12. If more than one Master Unit is mounted to the same PC, use the Configurator to check for duplica-
tion in the master parameter settings.
13. Register the master parameters in the Master Unit(s).
14. Go to step 28.
15. Connect a Configurator to the Network.
16. Turn ON the power supply to all the Slaves.
17. Read the Network configuration from the Configurator.
18. Turn OFF the power supply to all the Slaves.
19. Create the master parameters for each Master Unit and save the parameters in files.
20. Turn ON the power supply to one PC (i.e., to one of the Master Units).
21. Switch the PC to PROGRAM mode.
22. Read the Network configuration from the Configurator.
23. Read the master parameter file for the Master Unit that has been turned ON from the master param-
eter editing screen.
24. Write the master parameters created in the above step 19.
25. Turn OFF the power supply to the PC (i.e., the Master Unit) and the Slaves.
26. Repeat the above steps beginning at step 20. for all Master Units.
27. Turn ON the power supply to all Masters and Slaves.
28. Remote I/O communications will start with the scan list enabled. (Communications will not start if
they have been set to be stopped at startup from the Configurator.) Use the software switches or
Configurator to start and stop remote I/O communications.
29. Confirm that the MS and NS indicators on all Master Units and Slaves are lit.
30. Read the Network configuration from the Configurator.
31. Save the Network configuration in a file from the Configurator.
32. Switch the PC to RUN mode.
CompoBus/D System Startup Chapter 4