112
Frequency setting by input signals
(2) Multi-speed setting for 4 or more speeds (Pr. 24 to Pr. 27)
Frequency from speed 4 to speed 7 can be set according to the
combination of the RH, RM and RL signals. Set the running frequencies
in Pr. 24 to Pr. 27 (In the initial value setting, speed 4 to speed 7 are
invalid).
REMARKS
Multi-speed setting using parameters is available even during PU operation.
Pr. 24 to Pr. 27 settings have no priority among them.
When Pr. 59 Remote function selection ≠ "0", multi-speed setting is invalid as RH, RM and RL signals are remote setting signals.
Parameters referred to
Pr. 59 Remote function selection Refer to page 113
ON ON ON
ON ON
ONON
ON
Speed 4
Speed 5
Speed 6
Speed 7
RH
RM
RL
Output frequency (Hz)