132
Selection and protection of a motor
(4) Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
<Operating procedure>
1) Set Pr. 71 according to the motor used.
2) In the parameter setting mode, read the following parameters and set desired values.
Motor Pr. 71 Setting ∗1
Mitsubishi standard motor
Mitsubishi high efficiency motor
SF-JR 4
SF-JR 4P 1.5kW or less 24
SF-HR 44
Others 4
Mitsubishi constant-torque motor
SF-JRCA 4P 14
SF-HRCA 54
Others (SF-JRC, etc.) 14
Other manufacturer's
standard motor
-4
Other manufacturer's
constant-torque motor
-14
∗1 For other settings of Pr.71, refer to page 125.
Parameter
Number
Name Setting Range
Setting
Increments
Initial
Value
82 Motor excitation current 0 to ****, 9999 1 9999
90 Motor constant (R1) 0 to ****, 9999 1 9999
91 Motor constant (R2) 0 to ****, 9999 1 9999
92 Motor constant (L1) 0 to ****, 9999 1 9999
93 Motor constant (L2) 0 to ****, 9999 1 9999
94 Motor constant (X) 0 to ****, 9999 1 9999
859 Torque current 0 to ****, 9999 1 9999
REMARKS
When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants are used.
As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting:
Setting example To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed as "2516",
set 2642 (2516 x 1.05=2641.8) in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addition of a given
value to the displayed value has no significance.)