Causes and corrective actions
6.3 Causes and corrective actions
(1) Error message
A message regarding operational troubles is displayed. Output is not shutoff.
Operation panel
indication
HOLD
Name
Operation panel lock
Description
Operation lock mode is set. Operation other than is invalid. (Refer to page 184)
Check point
--------------
Corrective action
Press for 2s to release lock.
Operation panel
indication
LOCd
Name
Password locked
Description
Password function is active. Display and setting of parameter is restricted.
Check point
--------------
Corrective action
Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating. (Refer to page
169).
Operation panel
indication
Er1
Name
Write disable error
Description
You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to disable parameter
write.
Frequency jump setting range overlapped.
Check point
Check the setting of Pr. 77 Parameter write selection. (Refer to page 166).
Check the settings of Pr. 31 to Pr. 36 (frequency jump). (Refer to page 106)
Operation panel
indication
Er2
Name
Write error during operation
Description
When parameter write was performed during operation with a value other than "2" (writing is enabled independently
of operation status in any operation mode) is set in Pr. 77 and the STF (STR) is ON.
Check point
Check the Pr. 77 setting. (Refer to page 166).
Check that the inverter is not operating.
Corrective action
Set "2" in Pr. 77.
After stopping operation, make parameter setting.
Operation panel
indication
Er4
Name
Mode designation error
Description
Appears if a parameter setting is attempted in the NET operation mode with Pr. 77 "2."
Check point
Check that operation mode is PU operation mode.
Check the Pr. 77 setting. (Refer to page 166).
Corrective action
After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to page 212)
After setting Pr. 77 = "2", make parameter setting.
Operation panel
indication
Err.
Name
Inverter reset
Description
Appears when a reset command is executed by an error reset of FL remote communication and on the
operation panel.
Appears at power-OFF.
Corrective action
Turn OFF the reset command