Mitsubishi Electronics FR-E700 Marine Battery User Manual


 
172
Special operation and frequency control
(1) Jog operation from the operation panel
Selects Jog operation mode from the operation panel. Operation is performed only while the start button is pressed.
Operation Display
1.
Confirmation of the RUN indicator and
operation mode indicator
The monitor mode should have been
selected.
The inverter should be at a stop.
2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication.
3. Press to choose the PU Jog operation
mode.
4. Press .
While is pressed, the motor rotates.
The motor runs at 5Hz. (Pr. 15 initial value)
Hold down.
5. Release
Release
[When changing the frequency of PU Jog operation]
6. Press to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously
appears.)
7. Turn until Pr. 15 Jog frequency appears.
8. Press to show the currently set value.
(5Hz)
9. Turn to set the value to " ".
(10Hz)
10.Press to set.
Flicker...Parameter setting complete!!
11. Perform the operations in steps 1 to 5.
The motor rotates at 10Hz.
NOTE
When Pr. 29 Acceleration/deceleration pattern selection = "1" (S-pattern acceleration/deceleration A), the acceleration/
deceleration time is the period of time required to reach Pr. 3 Base frequency.
The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency.
During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 227))
Parameters referred to
Pr. 13 Starting frequency Refer to page 119
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments Refer to page 116
Pr. 29 Acceleration/deceleration pattern selection Refer to page 120