56
Cyclic transmission
(1) Control information (invertermaster)
<Slave status>
<Actual slave type>
<Simple setting check area>
Not used. (Displays data imported in the simple setting area set from the master.)
(2) Control information (masterinverter)
<Remote control area>
<Expected slave type>
Refer to <Actual slave type>
<Simple setting check area>
Not used
Value Slave status
0 FL remote network is not connected
1 FL remote network remote at a stop
2 FL remote network remote connection processing
3 FL remote network remote operating
4 Master is not present
5 Own node is disconnected
6 Setting error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Output points
H00 to H3F (One point to 64 point)
Input points
H00 to H3F (One point to 64 point)
Subsequent area
0: Not used, 1: Used
0: Input not used (0 point)
1: Input used
Subsequent area
0: Not used, 1:Used
0: Output not used (0 point)
1: Output used
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Remote control flag
0: Remote control stop
1: Remote control start
Not used