PARAMETERS
5
Special operation and frequency control
5.18 Special operation and frequency control
5.18.1Jog operation (Pr. 15, Pr. 16)
Purpose Parameter that should be Set Refer to Page
Perform jog operation Jog operation Pr. 15, Pr. 16 171
Frequency control appropriate for
load torque
Droop control Pr. 286, Pr. 287
173
Avoid overvoltage alarm due to
regeneration by automatic
adjustment of output frequency
Regeneration avoidance
function
Pr. 882, Pr. 883, Pr. 885, Pr. 886
174
You can set the frequency and acceleration/deceleration time for Jog operation. JOG operation can be performed from the
operation panel.
This operation can be used for conveyor positioning, test operation, etc.
Parameter
Number
Name
Initial
Value
Setting Range Description
15 Jog frequency
5Hz 0 to 400Hz Frequency for Jog operation.
16
Jog acceleration/
deceleration time
0.5s 0 to 3600/ 360s
Acceleration/deceleration time for Jog operation. As the acceleration/
deceleration time, set the time taken to reach the frequency (initial
value is 60Hz) set in Pr. 20 Acceleration/deceleration reference frequency.
Acceleration/deceleration time can not be set separately.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
When the Pr. 21 Acceleration/deceleration time increments setting is "0" (initial value), the setting range is "0 to 3600s" and setting increments is "0.1s". When
the setting is "1", the setting range is "0 to 360s" and the setting increments is "0.01s".