Mitsubishi Electronics FR-E700 Marine Battery User Manual


 
142
I/O signal control
5.11.2 Reset cancel signal (READY signal) and inverter running signal (RUN signal)
When the reset operation of the inverter is canceled, reset cancel signal (READY) is output.
When the output frequency of the inverter rises to or above Pr. 13 Starting frequency , the output of the inverter running signal
(RUN) is turned ON. During an inverter stop or DC injection brake operation, the output is OFF.
Inverter
Status
During
Reset
Operation
24V External
Power Supply
(EV Display
on the
Operation
Panel)
Start
Signal
OFF
(During
Stop)
Start
Signal
ON
(During
Stop)
Start
Signal
ON
(During
Operation)
Under
DC
Injection
Brake
Output
Shut Off
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Output
Signal
Start
Signal
ON
Start
Signal
OFF
READY OFF ON ON ON ON ON ON ON ON
RUN OFF OFF OFF OFF
ON OFF OFF OFF ON
When a fault occurs, the MRS signal is ON, or the safety stop function is active.
Time
Power supply
Output frequency
STF
RH
READY
Pr. 13 Starting frequency
ON OFF
ON OFF
ON OFF
ON
DC injection brake operation point
DC injection brake operation
RUN
ON OFF
Reset processing