137
PARAMETERS
5
Motor brake and stop operation
(4) Regenerative brake duty alarm output
100%: regenerative overvoltage protection operation value
[RB] appears on the operation panel when 85% of the
regenerative brake duty set in Pr. 70 is reached. If the
regenerative brake duty reaches 100% of the Pr. 70
setting, a regenerative overvoltage (E.OV1 to E.OV3)
occurs.
Note that [RB] is not displayed when Pr. 30 = "0".
REMARKS
Refer to page 25 to 28 for connecting the brake resistor (MRS type, MYS type), high-duty brake resistor (FR-ABR) and brake unit
(FR-BU2).
WARNING
The value set in Pr. 70 must not exceed the setting of the brake resistor used.
Otherwise, the resistor can overheat.
Parameters referred to
Pr. 57 Restart coasting time Refer to page 151
Regenerative brake
pre-alarm [RB]
Time
Not
displayed
Not
displayed
Displayed Displayed
100
85
Ratio of the brake
duty to the Pr. 70
setting (%)