PARAMETERS
5
Frequency setting by input signals
REMARKS
During Jog operation, the remote setting function is invalid.
CAUTION
When selecting this function, re-set the maximum frequency according to the machine.
Parameters referred to
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency Refer to page 105
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Refer to page 116
Setting frequency is "0"
Even when the remotely-set
frequency is cleared by turning
ON the RL (clear) signal after turn
OFF (ON) of both the RH and RM
signals, the inverter operates at
the remotely-set frequency stored
in the last operation if power is
reapplied before one minute has
elapsed since turn OFF (ON) of
both the RH and RM signals
When the remotely-set frequency
is cleared by turning ON the RL
(clear) signal after turn OFF (ON)
of both the RH and RM signals,
the inverter operates at the
frequency in the remotely-set
frequency cleared state if power is
reapplied after one minute has
elapsed since turn OFF (ON) of
both the RH and RM signals.
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
(Hz)
ON
Power supply
ON
ON
ON
ON
ON
Within 1 minute
Time
Remotely-set frequency
stored last time
Remotely-set frequency stored last time
Deceleration (RM)
OFF
Output frequency
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
(Hz)
ON
Power supply
ON
ON
ON
ON
ON
More than 1 minute
Operation is performed
at the set frequency 0Hz.
Remotely-set frequency
stored last time
1 minute
Time
Deceleration (RM)
OFF
Output frequency