4. CONTROL UNIT CONNECTIONS
4.4 Connecting the Synchronous Feed Encoder
I - 23
4.4 Connecting the Synchronous Feed Encoder
The ENC connector is used to connect the synchronous feed encoder. Use the CS050 or CS054
connector set (optional, with both ends) when manufacturing the R050 or R054 cable. (Refer to the
cable manufacturing drawings for details.)
Note that the synchronous feed encoder may be connected via the spindle drive unit.
ENC
Control unit
SKIP
DIO
EXT2
SERVO
1
EXT1
MAINTENANCE
ENC HANDLE
SIO
TERMINAL
IC CARD
DC24V
IN
SERVO
2
MITSUBISHI
MELDAS
C64
1
10
11
20
ENC
connector
pin No.
Synchronous feed encode
r
OSE1024-3-15-68
R054 cable
R050 cable
Connection when connecting via a spindle drive unit
Control unit
ENC
Spindle drive unit
CN-8
(Connection of 1st channel)
(Connection of 2nd channel)
PC1 2
PC1* 12
PB1 3
PB1* 13
PA1 4
PA1* 14
GND 1
GND 11
PC2 7
PC2* 17
PB2 8
PB2* 18
PA2 9
PA2* 19
GND 5
GND 15
4
14
3
13
2
12
1
11
4
14
3
13
2
12
1
11
Recommended adaptive connector
Connector: 10120-3000VE (Sumitomo 3M)
Case: 10320-52F0-008 (Sumitomo 3M)
<Caution>
• The wire material shall be a shielded stranded cable
equivalent to AWG22(0.3mm
2
) compliant with the
UL1061-2464 standards. The shield shall be connected
to the connector case’s GND plate.
• This cable is not available from Mitsubishi.
CAUTION
Incorrect connections could cause device damage, so always connect the cables to the
designated connectors.
Do not connect or disconnect the connection cable between each unit while the power is
ON.