Function assignment of external terminal and control
4
PARAMETERS
4.10 Function assignment of external terminal and control
4.10.1 Input terminal function selection (Pr. 178 to Pr. 182)
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Purpose Parameter that should be Set Refer to Page
Assign function to input terminal
Input terminal function
selection
Pr. 178 to Pr. 182
113
Set MRS signal (output shutoff) to
NC contact specification
MRS input selection Pr. 17
115
Assign start signal and forward/
reverse command to other signals
Start signal (STF/STR)
operation selection
Pr. 250
117
Assign function to output terminal
Output terminal function
assignment
Pr. 190, Pr. 192
119
Detect output frequency
Up-to-frequency
sensitivity
Output frequency
detection
Pr. 41 to Pr. 43
123
Detect output current
Output current detection
Zero current detection
Pr. 150 to Pr. 153, Pr. 166, Pr. 167
124
Remote output function Remote output Pr. 495, Pr. 496
126
Use these parameters to select/change the input terminal functions.
Parameter
Number
Name
Initial
Value
Initial Signal Setting Range
178
STF terminal function
selection
60 STF (forward rotation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 60, 62, 65 to 67, 9999
179
STR terminal function
selection
61 STR (reverse rotation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 61, 62, 65 to 67, 9999
180
RL terminal function
selection
0 RL (low-speed operation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 62, 65 to 67, 9999
181
RM terminal function
selection
1
RM (middle speed operation
command)
182
RH terminal function
selection
2
RH (high-speed operation
command)