Communication operation and setting
Parameter
Faults history
Fault code list
(7) Pr. 343 Communication error count
You can check the cumulative number of communication errors.
Parameter Register Parameter Name
Read/
Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list (page
56) for the parameter names.
Read/write
The parameter number + 41000 is the register
number.
C2(902) 41902
Terminal 2 frequency setting
bias frequency
Read/write
C3(902)
42092
Terminal 2 frequency setting bias
(Analog value)
Read/write The analog value (%) set to C3 (902) is read.
43902
Terminal 2 frequency setting bias
(Terminal analog value)
Read
The analog value (%) of the voltage (current)
applied to the terminal 2 is read.
125(903) 41903
Terminal 2 frequency setting gain
frequency
Read/write
C4(903)
42093
Terminal 2 frequency setting gain
(Analog value)
Read/write The analog value (%) set to C4 (903) is read.
43903
Terminal 2 frequency setting gain
(Terminal analog value)
Read
The analog value (%) of the voltage (current)
applied to the terminal 2 is read.
C5(904) 41904
Terminal 4 frequency setting bias
frequency
Read/write
C6(904)
42094
Terminal 4 frequency setting bias
(Analog value)
Read/write The analog value (%) set to C6 (904) is read.
43904
Terminal 4 frequency setting bias
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905) 41905
Terminal 4 frequency setting
gain frequency
Read/write
C7(905)
42095
Terminal 4 frequency setting gain
(Analog value)
Read/write The analog value (%) set to C7 (905) is read.
43905
Terminal 4 frequency setting gain
(Terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
Register Definition Read/write Remarks
40501 Fault history 1 Read/write
Being 2 bytes in length, the data is stored as
"H00".
Refer to the lowest 1 byte for the error code.
Performing write using the register 40501 batch-
clears the faults history.
Set any value as data.
40502 Fault history 2 Read
40503 Fault history 3 Read
40504 Fault history 4 Read
40505 Fault history 5 Read
40506 Fault history 6 Read
40507 Fault history 7 Read
40508 Fault history 8 Read
Parameter Setting Range
Minimum
Setting Range
Initial Value
343 (Reading only) 1 0
NOTE
The number of communication errors is temporarily stored into the RAM. As it is not stored into the EEPROM
performing a power supply reset or inverter reset clears the value to 0.
Data
Definition
H00
No fault
present
H10 E.OC1
H11 E.OC2
H12 E.OC3
H20 E.OV1
H21 E.OV2
H22 E.OV3
H30 E.THT
H31 E.THM
H40 E.FIN
H52 E.ILF
H60 E.OLT
H70 E.BE
H80 E.GF
H81 E.LF
H90 E.OHT
H91 E.PTC
Data
Definition
HB0 E.PE
HB1 E.PUE
HB2 E.RET
HC0 E.CPU
HC4 E.CDO
HC5 E.IOH
HC7 E.AIE
HF5 E.5
Data
Definition
* Refer to page 249 for details of fault definition.