Mitsubishi Electronics FR-D720S-008 Marine Battery User Manual


 
183
Communication operation and setting
4
PARAMETERS
4.19.2 Initial settings and specifications of RS-485 communication
(Pr. 117 to Pr. 120, Pr. 123, Pr. 124, Pr. 549)
Used to perform required settings for RS-485 communication between the inverter and personal computer.
Use PU connector of the inverter for communication.
You can perform parameter setting, monitoring, etc. using Mitsubishi inverter protocol or Modbus-RTU protocol.
To make communication between the personal computer and inverter, setting of the communication specifications
must be made to the inverter in advance.
Data communication cannot be made if the initial settings are not made or there is any setting error.
Parameter
Number
Name
Initial
Value
Setting Range Description
117
PU communication
station number
0
0 to 31 (0 to 247)
∗1
Inverter station number specification
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
118 PU communication speed
192 48, 96, 192, 384
Communication speed
The setting value X 100 equals to the
communication speed.
Example)19200bps if 192
119
PU communication stop
bit length
1
Stop bit length Data length
0 1bit
8bit
1 2bit
10 1bit
7bit
11 2bit
120
PU communication parity
check
2
0 Without parity check
1 With odd parity check
2 With even parity check
123
PU communication
waiting time setting
9999
0 to 150ms
Set the waiting time between data transmission to
the inverter and response.
9999 Set with communication data.
124
PU communication CR/LF
selection
1
0 Without CR/LF
1With CR
2 With CR/LF
549 Protocol selection
0
0 Mitsubishi inverter (computer link operation) protocol
1 Modbus-RTU protocol
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
∗1 When "1" (Modbus-RTU protocol) is set in Pr. 549, the setting range within parenthesis is applied.
NOTE
Always reset the inverter after making the initial settings of the parameters. After you have changed the
communication-related parameters, communication cannot be made until the inverter is reset.