Mitsubishi Electronics FR-D720S-008 Marine Battery User Manual


 
4
Inverter and peripheral devices
1.2.1 Peripheral devices
Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity.
Refer to the following list and prepare appropriate peripheral devices:
∗1 Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
∗2 For installations in the United States or Canada, use the class T type fuse certified by the UL and cUL.
∗3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
Inverter Type
Motor
Output
(kW (HP))
Moulded Case Circuit Breaker (MCCB) ∗1
or Earth Leakage Circuit Breaker (ELB) ∗2
Magnetic Contactor (MC) ∗3
Reactor connection Reactor connection
without with without with
Three-Phase 200V
FR-D720-008 0.1 (1/8) 30AF 5A 30AF 5A S-N10 S-N10
FR-D720-014 0.2 (1/4) 30AF 5A 30AF 5A S-N10 S-N10
FR-D720-025 0.4 (1/2) 30AF 5A 30AF 5A S-N10 S-N10
FR-D720-042 0.75 (1) 30AF 10A 30AF 5A S-N10 S-N10
FR-D720-070 1.5 (2) 30AF 15A 30AF 10A S-N10 S-N10
FR-D720-100 2.2 (3) 30AF 20A 30AF 15A S-N10 S-N10
FR-D720-165 3.7 (5) 30AF 30A 30AF 30A S-N20, S-N21 S-N10
FR-D720-238 5.5 (7.5) 50AF 50A 50AF 40A S-N20, S-N21 S-N20, S-N21
FR-D720-318 7.5 (10) 100AF 60A 50AF 50A S-N25 S-N20, S-N21
Three-Phase 400V
FR-D740-012 0.4 (1/2) 30AF 5A 30AF 5A S-N10 S-N10
FR-D740-022 0.75 (1) 30AF 5A 30AF 5A S-N10 S-N10
FR-D740-036 1.5 (2) 30AF 10A 30AF 10A S-N10 S-N10
FR-D740-050 2.2 (3) 30AF 15A 30AF 10A S-N10 S-N10
FR-D740-080 3.7 (5) 30AF 20A 30AF 15A S-N10 S-N10
FR-D740-120 5.5 (7.5) 30AF 30A 30AF 20A S-N20 S-N11, S-N12
FR-D740-160 7.5 (10) 30AF 30A 30AF 30A S-N20 S-N20
Single-Phase 200V
FR-D720S-008 0.1 (1/8) 30AF 5A 30AF 5A S-N10 S-N10
FR-D720S-014 0.2 (1/4) 30AF 5A 30AF 5A S-N10 S-N10
FR-D720S-025 0.4 (1/2) 30AF 10A 30AF 5A S-N10 S-N10
FR-D720S-042 0.75 (1) 30AF 15A 30AF 10A S-N10 S-N10
FR-D720S-070 1.5 (2) 30AF 30A 30AF 15A S-N10 S-N10
FR-D720S-100 2.2 (3) 30AF 40A 30AF 30A S-N20, S-N21 S-N10
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the inverter type
and cable and reactor according to the motor output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter,
etc. Identify the cause of the trip, then remove the cause and power on the breaker.
MCCB INV
MCCB INV
IM
IM