Mitsubishi Electronics FR-D720S-008 Marine Battery User Manual


 
114
Function assignment of external terminal and control
(1) Input terminal function assignment
Using Pr. 178 to Pr. 182, set the functions of the input terminals.
Refer to the following table and set the parameters:
∗1 When Pr. 59 Remote function selection "0", the functions of the RL, RM and RH signals are changed as given in the table.
∗2 The OH signal turns ON when the relay contact "opens".
(2) Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
Setting Signal Function Related Parameters
Refer to
Page
0RL
Pr. 59 = 0 (initial value) Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr.232 to Pr.239
89
Pr. 59 0 ∗1 Remote setting (setting clear) Pr. 59 93
1RM
Pr. 59 = 0 (initial value) Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
89
Pr. 59 0 ∗1 Remote setting (deceleration) Pr. 59 93
2RH
Pr. 59 = 0 (initial value) High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
89
Pr. 59 0 ∗1 Remote setting (acceleration) Pr. 59 93
3 RT Second function selection Pr. 44 to Pr. 51 116
4 AU Terminal 4 input selection Pr. 267 150
5 JOG Jog operation selection Pr. 15, Pr. 16 91
7 OH External thermal relay input ∗2 Pr. 9 100
8REX
15-speed selection (combination with three speeds RL, RM,
RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
89
10 X10 Inverter run enable signal (FR-HC, FR-CV connection) Pr. 30, Pr. 70 110
12 X12 PU operation external interlock Pr. 79 165
14 X14 PID control valid terminal Pr. 127 to Pr. 134 212
16 X16
PU-external operation switchover (turning ON X16 selects
external operation)
Pr. 79, Pr. 340 172
18 X18 V/F switchover (V/F control is exercised when X18 is ON) Pr. 80 75, 105
24 MRS Output stop Pr. 17 115
25 STOP Start self-holding selection 117
60 STF
Forward rotation command (assigned to STF terminal (Pr. 178)
only)
117
61 STR
Reverse rotation command (assigned to STR terminal (Pr. 179)
only)
117
62 RES Inverter reset
65 X65
PU/NET operation switchover (turning ON X65 selects PU
operation)
Pr. 79, Pr. 340 173
66 X66
External/NET operation switchover (turning ON X66 selects
NET operation)
Pr. 79, Pr. 340 173
67 X67
Command source switchover (turning ON X67 makes Pr. 338
and Pr. 339 commands valid)
Pr. 338, Pr. 339 176
9999 No function
NOTE
Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect the other functions.
Make setting after confirming the function of each terminal.
One function can be assigned to two or more terminals. In this case, the terminal inputs are ORed.
The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the X10 signal (FR-HC, FR-CV connection-inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned with Pr.79 Operation mode selection set to "7", the MRS signal shares this
function.
Same signal is used to assign multi-speed (7th speed) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7th speed) setting and remote setting are not used to set speed at the same
time.)
When V/F control is selected by V/F switchover (X18 signal), second function is also selected at the same time.
Control between V/F and General-purpose magnetic flux can not be switched during operation. In case control is
switched between V/F and General-purpose magnetic flux, only second function is selected.
Turning the AU signal ON makes terminal 2 (voltage input) invalid.