82
Adjust the output torque (current) of the motor
(6) Limit the stall prevention operation and fast-response current limit operation according to the
operating status (Pr. 156)
Refer to the following table and select whether stall prevention operation and fast-response current limit operation will be
performed or not and the operation to be performed at OL signal output.
∗1
When "Operation not continued for OL signal output" is selected, the fault (stopped by stall prevention) is displayed and operation is stopped.
∗2 Since stall prevention is not activated, OL signal and E.OLT are not output.
∗3 The settings "100" and "101" allow operations to be performed in the driving and regeneration modes, respectively. The setting "101" disables the fast-
response current limit in the driving mode.
Pr. 156
Setting
Fast-Response
Current Limit
: Activated
:
Not activated
Stall Prevention
Operation Selection
: Activated
:
Not activated
OL Signal
Output
:
Operation
continued
:
Operation
not continued
∗1
Pr. 156
Setting
Fast-Response
Current Limit
: Activated
:
Not activated
Stall Prevention
Operation Selection
: Activated
:
Not activated
OL Signal
Output
:
Operation
continued
:
Operation
not continued
∗1
Acceleration
Constant
speed
Deceleration
Acceleration
Constant
speed
Deceleration
0
(initial
value)

16

1

17

2

18

3

19

4

20

5

21

6

22

7

23

8

24

9

25

10

26

11

27

12

28

13

29

14

∗2 30

∗2
15

∗2 31

∗2
100
∗3
Power driving

101
∗3
Power driving

Regeneration

∗2
Regeneration

∗2
NOTE
When the load is heavy or the acceleration/deceleration time is short, stall prevention is activated and acceleration/
deceleration may not be made according to the preset acceleration/deceleration time. Set Pr. 156
and stall prevention
operation level to the optimum values.
In vertical lift applications, make setting so that the fast-response current limit is not activated. Torque may not be
produced, causing a load drop due to gravity.
CAUTION
Do not set a small value as the stall prevention operation current.
Otherwise, torque generated will reduce.
Test operation must be performed.
Stall prevention operation during acceleration may increase the acceleration time.
Stall prevention operation performed during constant speed may cause sudden speed changes.
Stall prevention operation during deceleration may increase the deceleration time, increasing the deceleration
distance.
Parameters referred to
Pr. 3 Base frequency Refer to page 85
Pr. 178 to Pr. 182 (input terminal function selection) Refer to page 113
Pr. 190, Pr. 192 (output terminal function selection) Refer to page 119