Causes and corrective actions
5.3 Causes and corrective actions
(1) Error message
A message regarding operational troubles is displayed. Output is not shutoff.
Operation panel
indication
HOLD
Name
Operation panel lock
Description
Operation lock mode is set. Operation other than is invalid. (Refer to page 239)
Check point
--------------
Corrective action
Press for 2s to release lock.
Operation panel
indication
LOCd
Name
Password locked
Description
Password function is active. Display and setting of parameter is restricted.
Check point
--------------
Corrective action
Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating. (Refer to page
163).
Operation panel
indication
Er1
Name
Write disable error
Description
1. You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to disable parameter
write.
2. Frequency jump setting range overlapped.
3. The PU and inverter cannot make normal communication.
Check point
1. Check the setting of Pr. 77 Parameter write selection. (Refer to page 161).
2. Check the settings of Pr. 31 to Pr. 36 (frequency jump). (Refer to page 84)
3. Check the connection of the PU and inverter.
Operation panel
indication
Er2
Name
Write error during operation
Description
When parameter write was performed during operation with a value other than "2" (writing is enabled independently
of operation status in any operation mode) is set in Pr. 77 and the STF (STR) is on.
Check point
1. Check the Pr. 77 setting. (Refer to page 161).
2. Check that the inverter is not operating.
Corrective action
1. Set "2" in Pr. 77.
2. After stopping operation, make parameter setting.
Operation panel
indication
Er3
Name
Calibration error
Description
Analog input bias and gain calibration values are too close.
Check point
Check the settings of C3, C4, C6 and C7 (calibration functions). (Refer to page 153).
Operation panel
indication
Er4
Name
Mode designation error
Description
You attempted to make parameter setting in the NET operation mode when Pr. 77 is not 2.
Check point
1. Check that operation mode is PU operation mode.
2. Check the Pr. 77 setting. (Refer to page 161).
Corrective action
1. After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to page 165)
2. After setting "2" in Pr. 77, make parameter setting.