Parameter List
Automatic acceleration/deceleration
61
Reference current
0.01A 9999
0 to 500A Setting value (rated motor current) is referenced
9999 Rated inverter current is referenced
62
Reference value at
acceleration
0.1% 9999
0 to 220%
Setting value is a limit
value
Shortest acceleration/
deceleration mode
Setting value is an
optimum value
Optimum acceleration/
deceleration mode
9999
150% is a limit value
Shortest acceleration/
deceleration mode
100% is an optimum value
Optimum acceleration/
deceleration mode
63
Reference value at
deceleration
0.1% 9999
0 to 220%
Setting value is a limit
value
Shortest acceleration/
deceleration mode
Setting value is an
optimum value
Optimum acceleration/
deceleration mode
9999
150% is a limit value
Shortest acceleration/
deceleration mode
100% is an optimum value
Optimum acceleration/
deceleration mode
64
Starting frequency for
elevator mode
0.01Hz 9999
0 to 10Hz 0 to 10Hz are starting frequency
9999 2Hz is starting frequency
292
Automatic acceleration/
deceleration
10
0 Normal mode
3 Optimum acceleration/deceleration mode
5 Elevator mode 1
6 Elevator mode 2
7 Brake sequence mode 1
8 Brake sequence mode 2
11 Shortest acceleration/deceleration mode
293
Acceleration/deceleration
separate selection
10
0
Calculate acceleration/deceleration time of both
acceleration and deceleration for the shortest and
optimum acceleration/deceleration mode.
1
Calculate only acceleration time for the shortest and
optimum acceleration/deceleration mode
2
Calculate only deceleration time for the shortest and
optimum acceleration/deceleration mode
Retry function at alarm
occurrence
65
Retry selection
1 0 0 to 5 A fault for retry can be selected.
67
Number of retries at fault
occurrence
10
0 No retry function
1 to 10
Set the number of retries at fault occurrence. A fault
output is not provided during retry operation.
101 to 110
Set the number of retries at fault occurrence. (The
setting value -100 is the number of retries.) A fault
output is provided during retry operation.
68
Retry waiting time
0.1s 1s 0 to 10s
Set the waiting time from when an inverter fault
occurs until a retry is made.
69
Retry count display erase
1 0 0 Clears the number of restarts succeeded by retry.
—
66
Refer to Pr. 22 and Pr. 23.
67 to 69
Refer to Pr. 65.