140
Parameter List
Adjustment of analog input torque magnetic flux command
(calibration)
C16
(919)
Terminal 1 bias command
(torque/magnetic flux)
0.1% 0% 0 to 400%
Set the torque/magnetic flux command value on the
bias side of terminal 1 input. (valid when Pr. 868 0,
5)
C17
(919)
Terminal 1 bias (torque/
magnetic flux)
0.1% 0% 0 to 300%
Set the converted % of the bias side voltage
(current) of terminal 1 input. (valid when Pr. 868 0,
5)
C18
(920)
Terminal 1 gain command
(torque/magnetic flux)
0.1% 150% 0 to 400%
Set the torque/magnetic flux command value on the
gain side of terminal 1 input. (valid when Pr. 868 0,
5)
C19
(920)
Terminal 1 gain (torque/
magnetic flux)
0.1% 100% 0 to 300%
Set the converted % of the gain side voltage
(current) of terminal 1 input. (valid when Pr. 868 0,
5)
C38
(932)
Terminal 4 bias command
(torque/magnetic flux)
0.1% 0% 0 to 400%
Set the torque/magnetic flux command value on the
bias side of terminal 4 input. (valid when Pr. 858 = 1,
4)
C39
(932)
Terminal 4 bias (torque/
magnetic flux)
0.1% 20% 0 to 300%
Set the converted % of the bias side current (voltage)
of terminal 4 input. (valid when Pr. 858 = 1, 4)
C40
(933)
Terminal 4 gain command
(torque/magnetic flux)
0.1% 150% 0 to 400%
Set the torque/magnetic flux command value on the
bias side of terminal 4 input. (valid when Pr. 858 = 1,
4)
C41
(933)
Terminal 4 gain (torque/
magnetic flux)
0.1% 100% 0 to 300%
Set the converted % of the gain side current (voltage)
of terminal 4 input. (valid when Pr. 858 = 1, 4)
989
Parameter for manufacturer setting. Do not set.
Buzzer control
of the operation
panel
990
PU buzzer control
11
0 Without buzzer
1 With buzzer
PU contrast
adjustment
991
PU contrast adjustment
1 58 0 to 63
Contrast adjustment of the LCD of the parameter unit
(FR-PU04/FR-PU07) can be performed.
0 (Light) 63 (Dark)
Parameter clear,
parameter copy
Pr.CL
Parameter clear
100, 1
Setting "1" returns all parameters except calibration
parameters to the initial values.
ALLC
All parameter clear
1 0 0, 1 Setting "1" returns all parameters to the initial values.
Er.CL
Faults history clear
1 0 0, 1 Setting "1" will clear eight past faults.
PCPY
Parameter copy
10
0 Cancel
1 Read the source parameters to the operation panel.
2
Write the parameters copied to the operation panel to
the destination inverter.
3 Verify parameters in the inverter and operation panel.
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Func
t
ion
Parameter
Name
Incre
ments
Initial
Value
Range Description
Related
parameters