Mitsubishi Electronics FR-A701 Marine Battery User Manual


 
138
Parameter List
Torque detection
864
Torque detection
0.1% 150% 0 to 400%
You can make setting to output a signal if the motor
torque exceeds the predetermined value.
865
Refer to Pr. 41.
866
Refer to Pr. 55.
867
Refer to Pr. 52.
868
Refer to Pr. 858.
872
Refer to Pr. 251.
Speed limit during
speed control
873
Speed limit
0.01Hz
20Hz
0 to 120Hz
Frequency is limited at the set frequency + Pr.873
during vector control.
874
Refer to Pr. 22.
Fault definition
875
Fault definition
10
0
At occurrence of any fault, output is shut off
immediately. At this time, the fault output also turns
on.
1
At occurrence of external thermal operation (OHT),
electronic thermal relay function (THM) or PTC
thermistor function (PTC) fault, the motor is
decelerated to a stop.
At occurrence of fault other than OHT, THM and
PTC, trips immediately. Same operation as when "0"
is set is performed under position control.
877 to 881
Refer to Pr. 828.
Regeneration avoidance function
882
Regeneration avoidance
operation selection
10
0 Regeneration avoidance function invalid
1 Regeneration avoidance function is always valid
2
Regeneration avoidance function is valid only at
constant speed
883
Regeneration avoidance
operation level
0.1V
380/
760VDC
*
300 to 800V
Set the bus voltage level at which regeneration
avoidance operates. When the bus voltage level is
set to low, overvoltage error will be less apt to occur.
However, the actual deceleration time increases.
The set value must be higher than the power supply
voltage
×
* The initial value differs according to the voltage level.
(200V class / 400V class)
884
Regeneration avoidance at
deceleration detection
sensitivity
10
0
Regeneration avoidance by bus voltage change ratio
is invalid
1 to 5
Set sensitivity to detect the bus voltage change.
Setting: 1 5
Detection sensitivity: Low High
885
Regeneration avoidance
compensation frequency limit
value
0.01Hz 6Hz
0 to 10Hz
Set the limit value of frequency which rises at
activation of regeneration avoidance function.
9999 Frequency limit invalid
886
Regeneration avoidance
voltage gain
0.1% 100% 0 to 200%
Adjust responsiveness at activation of regeneration
avoidance. Setting a larger value in Pr.886 will
improve responsiveness to the bus voltage change.
However, the output frequency could become
unstable. When vibration is not suppressed by
decreasing the Pr.886 setting, set a smaller value in
Pr.665.
665
Regeneration avoidance
frequency gain
0.1% 100% 0 to 200%
Free
parameter
888
Free parameter 1
1 9999 0 to 9999
Parameters you can use for your own purposes.
Used for maintenance, management, etc. by setting
a unique number to each inverter when multiple
inverters are used.
889
Free parameter 2
1 9999 0 to 9999
891
Refer to Pr. 52.
Func
t
ion
Parameter
Name
Incre
ments
Initial
Value
Range Description
Related
parameters
Sensorless
Sensorless
Sensorless Vector
Vector
Vector
Vector
Vector
Vector
2